Back to www.openers-closers.com
5F0B21 Electric Strike

5F0B21

5F0B21 Series 5 Electric Strike Fire/Smoke 6-14V AC/DC 10,000N Fail-secure

Technical Data

FunctionFail-secure
OperationFail-secure
Resistance to forced entry10,000 N
Endurance Rating (Cycles)200,000
Operating Temperature-10ºC − +55ºC
Sound Level AC (at 50 cm)69 dBA
Sound Level DC (at 50 cm)5 dBA
Latch Spring Force40-44 N
Door Opening Direction (DIN 107)DIN R / DIN L
Vertical and Horizontal InstallationYes
Strike Fixing Distance52.3 mm
Height (Z)65.5 mm
Width (X)17.4 mm
Depth (Y)28 mm
KeeperAdjustable
Radian KeeperInternal
Keeper Movement25º
Keeper Depth6 mm
Keeper Adjustment3 mm
Suitable for Fire/Smoke Protection DoorsFire/Smoke 90 min

Product Certificates

Regulations(UE) 305/2011
StandardsEN 14846:2008
CPR Certificate0432-CPR-00454-02
Certification AuthorityMPA DO 22.5
Classification
3C3E0H000
EMC Directive2014/30/UE
RoHS Directive2011/65/UE
REACH Regulation1907/2006

Connection

Connection 5F0B21 Electric Strike

Electrical Data (at 20°C)

CoilB
Nominal Voltage6-14V AC/DC
Rated Resistance8 Ω
Duty Cycle (%ED)<1min
Transient Voltage Suppressor (TVS)Yes
PCB Hardware VersionPCBA0000001

Consumption Tables showing relation between Tension (Vin), Consumption (A) and Preload Force (N)

Alternating Current (AC)

Vin (AC)

Initial

C0(A)1C1(A)2DIN L (N)4DIN R (N)5

Holding

C2(A)3
60.520.522002000.52
8
9
10
121.091.092002501.09
141.281.282202501.28
16
22
24
28
30

Direct Current (DC)

Vin (DC)

Initial

C0(A)1C1(A)2DIN L (N)4DIN R (N)5

Holding

C2(A)3
60.660.6640800.66
8
9
10
121.291.291001501.29
141.471.471101501.47
16
22
24
28
30
1 C0: Peak current. 2 C1: Initial Consumption. 3 C2: Holding Consumption. 4,5 Preload Force in Newtons (N) DIN L, DIN R (With preload, the strike processes the opening in under 1 second).
The table shows the test values at a temperature of 20°C; any variation in this condition will affect both the power consumption and the holding force of the electric strike. Consumption deviation of ±7% due to ohmic tolerance of coil.